This is an installation guide that introduces the installation and basic local configuration settings of the Unison Echo® contact and demand response interfaces.
The ETC Unison Echo Contact and Demand Response Interfaces are DIN rail mounted devices for Echo control systems. The guide covers the Input Interface with four momentary or maintained closures, the Demand Response Interface with four maintained closures, and the Output Interface with four normally open or normally closed relays.
It explains installation preparation, EchoConnect and 24 VDC wiring, input and output terminations, DIN rail mounting, and selection between Basic and Custom configuration modes. Custom settings are made with the EchoAccess Mobile App.
| Operating temperature | 0-50°C |
|---|---|
| Operating humidity | 0-95% non-condensing |
| External power | 24 VDC (Class 2) |
| Maximum current draw | 40mA during normal operation |
| Wire terminal range | 24-12 AWG (0.2 mm2-4 mm2) |
| EchoConnect maximum run length | 1,640 feet (500 m) |
| Output relay rating | 2A at 30 VAC or 30 VDC |
They require an external 24 VDC (Class 2) power supply in addition to EchoConnect.
The unit draws a maximum of 40mA during normal operation.
It may not exceed 1,640 feet (500 m) when using Belden 8471 or equivalent wire.
Each output is rated for 2A at 30 VAC or 30 VDC.