The DAU is a constant flow damper that facilitates balancing of ventilation systems and gives correct flow from the start. The unit compensates e.g. connection and disconnection of system parts, clogging of filters and ducts, thermal lift forces, wind effects, window opening etc. Ø 80-315 fullfills pressure class A in closed position. Fulfils tightness class C.
This document provides instructions for installing and operating the Lindab DAU constant flow damper, which maintains a set airflow regardless of pressure changes. It includes technical data on flow ranges, pressure, sound levels, and mounting requirements. The damper is manually adjustable and suitable for ventilation systems with diameters from Ø80 to Ø315. It can handle 50 mm duct insulation and is designed to be mounted in any direction without affecting accuracy.
The manual also details sound power levels across different frequencies and flow rates, and includes tables and graphs for pressure loss and velocity. It specifies that the device is calibrated at factory and maintains flow within ±5 to ±10% deviation. Mounting near disturbances may reduce accuracy, and a minimum straight duct distance is required for optimal performance.
| Flow Range | 15–830 l/s (54–2988 m³/h) |
|---|---|
| Pressure Range | 50–1000 Pa (over the unit) |
| Tightness Class | C |
| Material | Galvanized sheet metal housing and blade, stainless steel shaft |
| Temperature Range | +5 to +70 °C |
The flow is set by loosening the center nut, turning the scale arrow to the desired flow, then tightening the center nut.
The device maintains flow within ±5 to ±10% deviation across its working range, with larger deviation possible at lower flows.
Yes, the damper is independent of mounting direction and can be mounted in any orientation without affecting accuracy.
The DAU can handle 50 mm duct insulation without hiding the scale or motor. A version with 45 mm insulation and outer shell is called DALU.