Lindab Regula Master TCP Alarms Handling Guide

This document describes how to handle alarms in Regula Master TCP - the procedure and which commands to use


Lindab Regula Master TCP Alarms Handling Guide - cover page
Brand
Lindab
Document type
User Manual
Language
English
Pages
5
File format
PDF
File size
4 MB
Published
27 October, 2023
Updated
27 October, 2023
MD5 checksum
329D79B4A21986BC0D31E6B1D2682226

About this manual

This guide explains how to handle alarms in Lindab Regula Master TCP using Modbus/EXOline and BACnet protocols. Alarms are managed via specific register signals and commands. For Modbus/EXOline, alarm status is in discrete inputs and input registers, with commands in holding registers. For BACnet, alarms are shown as multi-state inputs with commands in analog value signals. Commissioning parameters for 26 SRCs can be read and written using specific procedures for each protocol.

What's inside

  • Alarms Handling
  • Modbus/EXOline TCP
  • BACnet TCP
  • SRC Commissioning Parameters
  • Reading and Writing Parameters

Frequently asked questions

How are alarms displayed in Modbus/EXOline TCP?

Alarms are shown in Discrete Inputs (for real-time monitoring) and Input registers (2000-2178) for status. Commands are in Holding registers 3000-3001.

What commands can be used to manage alarms in Modbus/EXOline TCP?

Commands include Acknowledge (1), Block (2), and Unblock (3). Cancelled or Returned alarms become Normal after Acknowledge.

How are alarms managed in BACnet TCP?

Alarms are shown as Multi-state Input signals (object instance 62-179) with values Normal(2), Blocked(3), Cancelled(4), Returned(6), Alarm(8). Commands are set in Analog Value-901 and Analog Value-902.