This document describes how to handle alarms in Regula Master TCP - the procedure and which commands to use
This guide explains how to handle alarms in Lindab Regula Master TCP using Modbus/EXOline and BACnet protocols. Alarms are managed via specific register signals and commands. For Modbus/EXOline, alarm status is in discrete inputs and input registers, with commands in holding registers. For BACnet, alarms are shown as multi-state inputs with commands in analog value signals. Commissioning parameters for 26 SRCs can be read and written using specific procedures for each protocol.
Alarms are shown in Discrete Inputs (for real-time monitoring) and Input registers (2000-2178) for status. Commands are in Holding registers 3000-3001.
Commands include Acknowledge (1), Block (2), and Unblock (3). Cancelled or Returned alarms become Normal after Acknowledge.
Alarms are shown as Multi-state Input signals (object instance 62-179) with values Normal(2), Blocked(3), Cancelled(4), Returned(6), Alarm(8). Commands are set in Analog Value-901 and Analog Value-902.