Somfy animeo LON 4 AC Motor Controller WM/DRM 220-240 V AC Installation Guide

This is an instruction manual for animeo LON 4 AC MOTOR CONTROLLER WM/DRM 220-240 V AC, which introduces the product's features and installation and use methods


Somfy animeo LON 4 AC Motor Controller WM/DRM 220-240 V AC Installation Guide - cover page
Brand
SOMFY
Category
Automation control Equipment
Document type
Installation Guide
Language
English
Pages
12
File format
PDF
File size
2.7 MB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
2B75A1233043E1B25C7721F21FB5F0A5

About this manual

The animeo LON 4 AC Motor Controller WM/DRM 220-240 V AC is documented under refs 1860119, 1860115 and 5051044B. The guide presents figures for mounting, wiring and commissioning, including the LON network and the Somfy subnet with up to four additional IB+ 4 AC Motor Controllers.

It describes local push-button inputs that can also be used as universal LON binary inputs, a Reset / Prog button for returning the controller to factory settings, and a heartbeat LED check after power-up. Cable and connection requirements are listed for motors, switches, group control, the LON bus, the LON Somfy subnet and the 220-240 V AC supply.

What's inside

  • Mounting
  • Wiring
  • Commissioning
  • Heartbeat
  • Reset / Prog button
  • LON Somfy Subnet
  • Group control
  • Local push button inputs

Specifications

Mains voltage220-240 V AC
Fuse ratingM4 F 3.15 AH
Somfy subnet capacityMaximum 4 additional IB+ 4 AC Motor Controllers
LON bus cable2 x 0.8 mm/20 AWG
LON Somfy Subnet extension lengthRequired 200 m

Frequently asked questions

What should I check if the heartbeat LED is missing on one or more motor controllers?

Check the power supply, the subnet wiring (1 to 1), the 120 Ohm terminating resistors at both ends of the subnet, and the IB+ Motor Controller version (at least E01).

How can I restore the LON 4 AC Motor Controller to factory settings?

Use the Reset / Prog button; after reset, existing subnet motor controllers are detected and initialized again.

What happens to the drives if the subnet connection is interrupted after commissioning?

After 0.5 minutes, all affected drives move to the safety position and are locked.

Can the local push button inputs be used as LON binary inputs?

Yes, the local push button inputs can be used as universal LON binary inputs.