KSTAR data communication site debugging instructions for Kstar photovoltaic grid-connected inverters, suitable for KSG-10K KSG-12K KSG-17K KSG-20K inverters
This V1.01 document covers site debugging of data communication for KSTAR (科士达) KSG-10K, KSG-12K, KSG-17K and KSG-20K photovoltaic grid-connected inverters, issued by Shanghai Taoke Network Technology Co., Ltd. on 2018-07-23. It describes monitoring system wiring, 485 cable and conduit requirements, collector installation, inverter RS485 wiring and parameter settings, registration processes, and troubleshooting.
It also includes common problems and solutions for unstable or missing data, plus the collector packing list. This manual is written in Chinese.
| Applicable inverter models | KSG-10K, KSG-12K, KSG-17K, KSG-20K |
|---|---|
| 485 communication cable diameter | ≥1.0 mm |
| Maximum connected device cable length per collector | 100 m |
| Minimum collector waterproof box size | 280.5 x 190.3 mm |
| Minimum distance from transformer | 2 m |
| Minimum distance from inverter | 1 m |
Use industrial-grade shielded communication cable; if network cable is used, use Cat5e shielded cable, and if 485 cable is used, use dedicated twisted shielded cable.
The effective length is 100 m; if it exceeds 100 m, add another collector.
The minimum size is 280.5 x 190.3 mm; smaller boxes are not warranted.
Check shielded twisted-pair cable, same-pair A/B wiring, inverter GND connection, cable length, terminal resistor settings, conduit, interference sources, and terminal connections.