Allen-Bradley MicroView 2707-MVH232/2707-MVP232 Operator Interface Module User Manual

This manual introduces the functions and usage instructions of the MicroView operator interface module used for controlling equipment.


Allen-Bradley MicroView 2707-MVH232/2707-MVP232 Operator Interface Module User Manual - cover page
Brand
Allen-Bradley
Category
Automation control Equipment
Document type
User Manual
Language
English
Pages
92
File format
PDF
File size
1.6 MB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
A5A7E20D69D0AB7F139A68C7CC73FCAE

About this manual

The MicroView Operator Interface Module user manual covers Allen-Bradley catalog numbers 2707-MVH232 and 2707-MVP232. It describes the front panel, display, keypad, communications port, and power connector, and explains how the unit interfaces with MicroLogix controllers.

The manual also gives procedures for initial setup, transferring applications, running applications, installation, RS-232 connections, and troubleshooting and maintenance. Appendixes cover specifications, cable diagrams, and special controller functions.

What's inside

  • MicroView Overview
  • Initial Setup and Mode Menu
  • Transferring Applications
  • Running Applications
  • Installing the MicroView Operator Interface
  • Communication Connections and Setup
  • Troubleshooting and Maintenance
  • Specifications
  • MicroView Cable Diagrams
  • MicroView Special Controller Functions

Specifications

LCD display2 lines x 16 characters
Character size (H x W)0.22 x 0.12 in (5.56 x 2.96 mm)
Character format5 x 7 dot matrix
BacklightYellow-green LED, fixed intensity
ContrastFixed
Display viewing area (H x W)0.58 x 2.35 in (15mm x 60 mm)
Keypad typeTactile embossed, domed keys, sealed membrane
Keypad operation force16 oz. (453 grams)
Keypad operational life1 million operations
Communications portRS-232
Communication distance50 ft. (15 meters) maximum
Input voltage range11-25 VDC, 1.5 Watt
Agency ratingUL, CSA, CE

Frequently asked questions

What is the MicroView used for?

It interfaces with MicroLogix controllers and lets operators monitor and manipulate process data on the plant floor.

What type of display does the MicroView use?

It uses a 2 line by 16 character high contrast LCD display with LED backlighting.

What communication port does the MicroView have?

It has an RS-232 communications port for point-to-point connections with a MicroLogix controller or an IBM-compatible PC.

How long can RS-232 communication distances be?

RS-232 communication distances are 50 ft. (15 meters) maximum.