This document is the user manual of Taiwan Juko A-1 series remote I/O modules, which introduces Modbus protocol, register address table, I/O module general use and communication debugging with other devices.
This is the user manual (V1.12, edited 2017/09/01) for the Taiwan Juko A-1 Series remote I/O modules. It introduces the Modbus protocol, explains the master/slave request-response process, the register areas and common function codes, and describes the RTU, ASCII and TCP frame formats used by the modules.
The manual then walks through basic hardware connection and parameter configuration with the YottaUtility software, including station number, baud rate, parity, stop bits and protocol settings, WiFi settings for the A-12xx modules and Ethernet settings for the A-18 series in Init mode. It also covers analog input jumper configuration for the A-1019/A-1219/A-1819 modules, debugging and communication with host software such as ModbusPoll, and ends with Modbus protocol address tables for the individual module models. This manual is written in Chinese.
| Station number | 1 to 255 (decimal) |
|---|---|
| Baud rate | 1200, 2400, 4800, 9600, 14.4K, 19.2K, 28.8K, 38.4K, 57.6K, 115.2K, 230.4K bps |
| Parity | None, Odd, Even |
| Data bits | 8 (not selectable) |
| Stop bits | 1, 2 |
| Communication protocol | Modbus-RTU, Modbus-ASCII |
| Power supply terminals | +VS positive, GND negative |
| RS-485 terminals | DATA+ (Y), DATA- (G) |
| Ethernet interface | RJ-45, A-18 series only |
| Analog input factory jumper setting | A PIN shorted for current 0/4-20 mA input |
Switch the switch on the back of the module to Init mode first, then power the module on. Connect it to the PC by RS-485, USB or Ethernet and open the YottaUtility software.
In Init mode the A-18 series module uses the IP address 192.168.1.1, which you enter in the Ethernet search field.
Each I/O module on the same bus should be set to a different Station number. If two or more modules must share a station number, they have to use different baud rates or protocols.
The A PIN is shorted for current input, the B PIN is shorted for thermistor input, and the A and B PINs are left open for thermocouple input. The factory setting is A PIN shorted for 0/4-20 mA current input.