Taiwan Juko A-1 Series Remote I/O Module User Manual

This document is the user manual of Taiwan Juko A-1 series remote I/O modules, which introduces Modbus protocol, register address table, I/O module general use and communication debugging with other devices.


Taiwan Juko A-1 Series Remote I/O Module User Manual - cover page
Brand
台湾巨控
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
40
File format
PDF
File size
1.6 MB
Published
31 October, 2023
Updated
31 October, 2023
MD5 checksum
0B24C0D150B9638E9E9DFA3E9CA07A11

About this manual

This is the user manual (V1.12, edited 2017/09/01) for the Taiwan Juko A-1 Series remote I/O modules. It introduces the Modbus protocol, explains the master/slave request-response process, the register areas and common function codes, and describes the RTU, ASCII and TCP frame formats used by the modules.

The manual then walks through basic hardware connection and parameter configuration with the YottaUtility software, including station number, baud rate, parity, stop bits and protocol settings, WiFi settings for the A-12xx modules and Ethernet settings for the A-18 series in Init mode. It also covers analog input jumper configuration for the A-1019/A-1219/A-1819 modules, debugging and communication with host software such as ModbusPoll, and ends with Modbus protocol address tables for the individual module models. This manual is written in Chinese.

What's inside

  • Modbus Protocol Introduction
  • Modbus Master-Slave Response Process
  • Modbus Register Areas and Common Function Codes
  • Modbus Frame Formats (RTU, ASCII, TCP)
  • Module Hardware Connection
  • Module Parameter Configuration
  • Analog Input Module Configuration (A-1019/A-1219/A-1819)
  • Debugging and Host Software Communication
  • Modbus Protocol Address Tables

Specifications

Station number1 to 255 (decimal)
Baud rate1200, 2400, 4800, 9600, 14.4K, 19.2K, 28.8K, 38.4K, 57.6K, 115.2K, 230.4K bps
ParityNone, Odd, Even
Data bits8 (not selectable)
Stop bits1, 2
Communication protocolModbus-RTU, Modbus-ASCII
Power supply terminals+VS positive, GND negative
RS-485 terminalsDATA+ (Y), DATA- (G)
Ethernet interfaceRJ-45, A-18 series only
Analog input factory jumper settingA PIN shorted for current 0/4-20 mA input

Frequently asked questions

How do I enter parameter configuration mode on an A-1 series module?

Switch the switch on the back of the module to Init mode first, then power the module on. Connect it to the PC by RS-485, USB or Ethernet and open the YottaUtility software.

What is the A-18 series IP address in Init mode?

In Init mode the A-18 series module uses the IP address 192.168.1.1, which you enter in the Ethernet search field.

Can several modules on the same bus use the same station number?

Each I/O module on the same bus should be set to a different Station number. If two or more modules must share a station number, they have to use different baud rates or protocols.

How are the analog input channels set for current, thermistor or thermocouple input?

The A PIN is shorted for current input, the B PIN is shorted for thermistor input, and the A and B PINs are left open for thermocouple input. The factory setting is A PIN shorted for 0/4-20 mA current input.