This document is a TCL air conditioner service manual, which introduces the details of TAC-09CHSD/XAB1I, TAC-12CHSD/XAB1I, TAC-18CHSD/XAB1I, TAC-24CHSD/XAB1I, TAC-09CHSD/XAB1IHB, TAC-12CHSD/XAB1IHB, TAC-18CHSD/XAB1IHB, TAC-24CHSD/XAB1IHB.
This TCL service manual covers the TAC-09CHSD/XAB1I, TAC-12CHSD/XAB1I, TAC-18CHSD/XAB1I and TAC-24CHSD/XAB1I inverter air conditioners, plus the TAC-09CHSD/XAB1IHB, TAC-12CHSD/XAB1IHB, TAC-18CHSD/XAB1IHB and TAC-24CHSD/XAB1IHB models.
Contents include important notice, product dimensions, refrigeration cycle diagram, operation details, wiring diagram, explosion view and parts, precaution, names of parts, installation, troubleshooting and an introduction to R32/R290 air conditioner installation. The manual states it is intended for individuals with adequate electrical, electronic and mechanical experience.
| Compressor restart delay | 3 minutes |
|---|---|
| 4-way valve delay | 2 minutes |
| Lower voltage protection | AC voltage ≤158 V for 10 seconds |
| Over voltage protection | AC voltage ≥260 V; recovery at ≤255 V |
| Cooling mode outdoor temperature cutoff | Compressor shuts down below -2 °C |
| Defrosting exit temperature | Outdoor coil temperature ≥15 °C |
| Indoor exchanger overheat protection | Above 55 °C |
It is intended for individuals with adequate electrical, electronic and mechanical experience.
The compressor is ceased for 3 minutes before restarting to balance the pressure in the refrigeration cycle.
The unit is shut down for protection.
Defrosting ends when outdoor coil temperature is at least 15 °C.