The fine mist fire extinguishing device is a fire extinguishing device that uses the fine mist fire extinguishing principle to spray water mist evenly on the fire site to form a mist curtain, isolate air and oxygen, and make the flame unable to burn, thereby achieving the purpose of extinguishing the fire. Fine mist fire extinguishing device has the advantages of fast extinguishing speed, non-toxic and harmless, and no pollution to the environment.
This is a Chinese-language user manual for a water mist fire extinguishing system. It is organized into five parts: the design parameters of the pump unit, the function description of the pump unit, the function description of the water tank, the function description of the control panel, and the periodic inspection procedures.
The pump unit uses high-pressure pumps from Danfoss, with one pump kept as a standby under normal conditions, plus a jockey pump and a standby jockey pump that hold the auxiliary pressure. The manual describes the water tank with its inlet solenoid valve, level switch, filter and drain valve, the operating, indicating and alarm functions of the control panel, and step-by-step test procedures for automatic changeover from main to emergency power, the control alarm system and the filter. This manual is written in Chinese.
| Water quality requirement | Potable water, compliant with the EU directive |
|---|---|
| Water tank type | Open stainless steel tank |
| Jockey pumps | One jockey pump and one standby jockey pump |
| High-pressure pump duty | One high-pressure pump acts as standby under normal conditions |
The manual specifies potable water that complies with the EU directive.
The level switch shuts down the high-pressure pumps. Once the tank is filled again the valve closes, and the pump can be restarted manually if it has been reset in the control box.
No. Dry running is prohibited, and after maintenance you must make sure the pump is properly filled with water before starting it.
When the water level reaches the set position, the inlet solenoid valve opens and water enters the tank.