DXN-Q High Voltage Live Display Locking Device Installation and Use Manual

DXN-Q high voltage live display locking device is used to indicate high voltage live, locking state information, and has phase checking and electricity testing functions.


DXN-Q High Voltage Live Display Locking Device Installation and Use Manual - cover page
Category
Other Electronics
Document type
Installation Guide
Language
Chinese
Pages
1
File format
PDF
File size
592 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
BD12D473DB7BD3F7F2F3A3BDB613203E

About this manual

The DXN-Q is a high-voltage live display locking device used in power-system ring main units, switchgear, and cable branch boxes to indicate live high voltage and lockout status, with phase-comparison and voltage-testing functions.

This one-page guide gives panel and mounting-hole dimensions, installation notes for the live-display and electromagnetic-lock sections, terminal wiring, supported external power supplies, and forced-lockout behavior. This manual is written in Chinese.

What's inside

  • Panel dimensions
  • Mounting hole dimensions
  • Live display section installation
  • Electromagnetic lock section installation
  • Wiring diagram and terminal connections
  • Capacitive sensor grounding
  • Supported external power supplies
  • Voltage threshold and forced lockout

Specifications

Panel dimensions96 mm (W) x 48 mm (H) x 80 mm (D)
Mounting hole dimensions92+0.6 mm (W) x 45+0.6 mm (H)
Supported external powerAC/DC 85-265 V, DC 24 V, DC 48 V
Forced lockout threshold15% to 45% of rated voltage on the three-phase high-voltage bus
Relay output contactsContacts 7 and 9 disconnect during forced lockout

Frequently asked questions

What external power supplies does the DXN-Q support?

It supports AC/DC 85-265 V, DC 24 V, and DC 48 V.

What happens when the three-phase high-voltage bus reaches 15% to 45% of rated voltage?

The relay output contacts 7 and 9 disconnect and the panel enters forced lockout.

How are the capacitive sensors connected?

Leads from the capacitive sensors on the electrical equipment connect to the L1, L2, L3, and ground terminals on the rear panel, and phase wiring errors must be avoided.

How are terminals 2 and 7 configured for active or passive lock contacts?

For active contacts, terminals 2 and 7 inside the host are shorted; for passive contacts, they are open.