MCW series water cooler user manual, which introduces the operating conditions, type, installation, debugging, maintenance, fault analysis and elimination, transportation requirements, storage requirements, scrapping, etc.
The MCW series water cooler is an industrial refrigeration unit built for machine tools, drive motors and motorized spindles, supplying a temperature-stable and precise cooling medium. The manual explains the refrigeration principle and the system components — compressor, condenser, evaporator, throttling device and refrigerant — and explains the model code, for example MCW-10C-01-1225, where 10 corresponds to a cooling capacity of 10×100 = 1000 W and C denotes a unit with tank and pump.
It lists the operating conditions and permitted and prohibited cooling media, then covers installation and piping, electrical connection, water filling and air bleeding, and the computer board settings and operation. Maintenance schedules for weekly, monthly, half-yearly and annual inspection are given, followed by a troubleshooting table and instructions for transport, storage and disposal. This manual is written in Chinese.
| Ambient temperature | 5 to 45 °C |
|---|---|
| Ambient humidity | ≤90%RH |
| Altitude | ≤3000 m |
| Power supply | Single-phase 220 V / 50 Hz |
| Cooling capacity code (example MCW-10...) | 10×100 = 1000 W |
| Permitted cooling media | Softened water (pure water, distilled water, high-purity water) |
| Permitted antifreeze addition | ≤30% ethylene glycol by volume, ≤20% ethanol by volume |
| Total pressure drop of connecting piping | ≤0.5 Bar |
| Piping pressure rating | At least 1.5 times the pump supply pressure |
| Maximum tilt during transport | ≤15° |
Softened water such as pure water, distilled water or high-purity water. An antifreeze addition of up to 30% ethylene glycol or 20% ethanol by volume is permitted.
An ambient temperature of 5 to 45 °C, humidity of 90%RH or less and an altitude of 3000 m or less.
No obstructions are allowed within 1 m of the air inlet and outlet, otherwise cooling performance is affected.
Gently turn the motor impeller by hand before switching on the power, because the water pump may otherwise be difficult to start.