About this manual

This is the user manual (V1.1) for the 智嵌物联 (ZQWL) 8-channel network relay controller, an industrial IO control board with 8 opto-isolated digital inputs compatible with NPN and PNP sensors, 8 relay outputs, one Ethernet port and one RS485 port. The manual states that all models in the table of applicable types share the same software functions and differ only in supply voltage, relay brand and housing; the examples use the ZQWL-IO-1CXRC8.

The document walks through hardware preparation, control with the ZQWL network IO configuration software, default parameters, control with a network debugging assistant, product specifications, hardware interfaces and dimensions, parameter configuration by software and web page, advanced features such as heartbeat packets, linkage control, delay-off and timer control, the custom, ASCII and Modbus RTU/TCP protocols, factory reset and firmware upgrade, application examples and troubleshooting. This manual is written in Chinese.

What's inside

  • About the manual and naming rules
  • Applicable models and related product downloads
  • Quick start: features and hardware preparation
  • Control with the configuration software
  • Control with the network debugging assistant
  • Product specifications (electrical, environment, EMC, relay, DI, communication)
  • Hardware interfaces and mechanical dimensions
  • Module parameter configuration (software and web page)
  • Advanced features (heartbeat, linkage, delay-off, timer, serial server)
  • Communication protocols (custom, ASCII, Modbus RTU, Modbus TCP)

Specifications

Supply voltage (12 V models)11 V min / 12 V typ / 13 V max
Supply voltage (24 V models)21 V min / 24 V typ / 25 V max
Operating current (all 8 relays on)350 mA typical (12 V models)
Digital inputs8 DI, NPN/PNP compatible
Relay outputs8 channels, load current selectable from 10 A to 30 A
Communication interfaces1 Ethernet port, 1 RS485 port
I/O count8 DI, 8 DO, 1 RS485, 1 RJ45
Operating and storage temperature-40 to 85 ℃
Operating humidity5~95%RH
ESD levelAir discharge ±15 kV, contact discharge ±8 kV
Default IP address192.168.1.253
Default work mode and local portTCP_SERVER, port 1030
Default RS485 baud rate115200, None/8/1
Housing (ZQWL-IO-1CXRC8 type)Rail mount, 145*90*40 mm (L*W*H)

Frequently asked questions

What is the default IP address and login for the controller?

The factory default IP address is 192.168.1.253 with subnet mask 255.255.255.0 and gateway 192.168.1.1; the web page user name and password are both admin.

What control protocols does the 8-channel network relay controller support?

It supports Modbus commands, ASCII control commands and a custom control protocol, and can also be controlled by the company's PC configuration software.

How many TCP clients can connect in TCP server mode?

Up to 4 clients can be connected when the device works in TCP server mode.

What power supply is needed to test the ZQWL-IO-1CXRC8?

A 12 VDC @ 1 A power supply is used in the test setup, with VCC to the positive (red) wire and GND to the negative (black) wire.

What is the default work mode and local port?

The device ships in TCP_SERVER mode with local port 1030 and RS485 set to 115200, None/8/1.