ygc-bg-m wall-mounted multi-in-one sensor can measure light intensity, temperature, humidity, co2 and other environmental elements, with high-grade shell, ip65 protection grade, rain and snow resistant and breathable. The product adopts American imported industrial grade microprocessor chip, Swiss imported high precision temperature and humidity chip, to ensure the excellent reliability, high precision and interchangeability of the product. The sensor can be easily connected with other acquisition devices and obtain data through rs485/rs232 output interface and standard modbus protocol. At the same time, the device can output up to 4 analog signals (current and voltage output). Digital signal output adopts standard modbus or ascii protocol, supports secondary development, stable and reliable, and is easy to install.
This manual describes the YGC-BG-M wall-mounted multi-in-one sensor from Wuhan Chenyun Technology Co., Ltd. (Yigood, www.yigood.net). The sensor is an integrated unit that measures environmental factors such as illuminance, temperature, humidity and CO2. It has an IP65-rated housing that resists rain and snow, uses an imported industrial-grade microprocessor chip and a Swiss high-precision temperature/humidity chip, and connects to data acquisition equipment through RS485/RS232 interfaces using the standard Modbus protocol. It can also output up to 4 analog signals (current or voltage).
The manual covers the selectable measurement elements and technical parameters, the model numbering table, wiring instructions with the color-coded wire order, analog output calculation formulas, wall-mounting installation steps, and the Modbus-RTU communication protocol including register addresses and example read commands for each sensor type. Applications include agricultural greenhouses, underground utility tunnels, industrial workshops, communication equipment rooms, warehouses, buildings and automation sites. This manual is written in Chinese.
| Air humidity range | 0~100%RH, ±3%RH, 0.1%RH resolution |
|---|---|
| CO2 range | 0~5000ppm, ±(50ppm+5%), 1ppm resolution |
| Power supply options | DC5V or DC9-30V |
| Output forms | 4-20mA, 0-20mA, 0-5V, 0-10V, 0-2.5V, 1-5V, RS485/RS232 (Modbus-RTU or ASCII) |
| Load capacity | 500 ohms (12V supply) |
| Protection rating | IP65 |
| Working environment | -40°C to +75°C |
| Communication | RS485 bus, Modbus-RTU, 9600 baud, 8 data bits, 1 stop bit, no parity, default address 1 |
| Cable length | Standard 2 meters |
Mark the hole positions on the wall at a 105mm hole spacing, drill with a φ5 hammer drill, insert the expansion tubes fully, then mount the sensor and tighten the screws.
Send the read command 01 03 00 00 00 01 84 0A to register 0; for example a returned value of 0x0026 equals decimal 38, which is 3.8°C with one decimal place.
Use Sensor_Value=(I-4)/16*Range+Sen_lower, where I is the measured current, Range is the sensor range and Sen_lower is the lower limit of the range.