This document is a planning and installation guide for Geberit FlowFit supply systems.
This document serves as a comprehensive planning and installation guide for the Geberit FlowFit supply system. It details the principles of the system, including its components and application range for potable water, heating, cooling, and compressed air installations. The guide provides specific instructions on the positioning, transport, and storage of the pipes to ensure they remain undamaged before installation.
| Operating temperature (hot water) | 0–70 °C |
|---|---|
| Short-time exposure temperature | up to 95 °C |
| Operating pressure (cold water) | 16 bar |
| Operating pressure (hot water) | 10 bar |
| Material composition | Multilayer PE-RT II / Al / PE-RT II |
Geberit FlowFit can be used for basement and riser pipes and storey distribution in potable water, heating, cooling, and compressed air installations.
The system is permanently rated for 0–70 °C, with short-time exposure up to 95 °C allowed for drinking water.
The system can handle 16 bar in cold water pipes where the operating temperature is between 0–20°C.
Rainwater must have a pH value greater than 6.0 to be suitable for use in the system.