This manual describes the installation, setup, operation and use of the SMC PLUS Controller. Basic installation and troubleshooting instructions apply to all of the SMC PLUS Controllers. The wiring and set-up procedures are for the SMC PLUS Controllers without options only. Wiring and set-up procedures fo the SMC PLUS Controllers with options can be found in the following publications: • 150-805 Soft Stop Option • 150-806 Pump Control Option • 150-807 Preset Slow Speed • 150-808 SMBTM Smart Motor Braking • 150-809 Accu-StopTM Option • 150-810 Slow Speed with Braking 1 Chapter Catalog Number Identification The following is an explanation of the catalog numbering system for the Bulletin 150 SMC PLUS Smart Motor Controller.
The manual describes the installation, setup, operation, and use of the SMC PLUS Smart Motor Controller. It covers catalog number identification for open and combination controllers, including ratings from 24 A to 135 A, enclosure types, voltage options, and optional functions such as Soft Stop, Pump Control, Preset Slow Speed, SMB Smart Motor Braking, Accu-Stop, and Slow Speed with Braking.
Detailed specifications are provided for input voltage (200–480 VAC or 200–600 VAC, 3-phase), control voltage (100–240 VAC, 1-phase), operating temperature (0°C to +50°C), and various protection features. Standard adjustments include soft start (2–30 s), initial torque (5–90% locked rotor torque), kickstart (500% current for 0.4–2 s), and current limit (50–500% full load amperes). Installation guidelines address enclosure ventilation, mounting clearances, heat dissipation, power and control wiring, and typical connection diagrams with and without isolation contactors.
| Input Voltage (Power Module) | 200–480 VAC, 3-phase, +10%, –15% or 200–600 VAC, 3-phase, +10%, –15% |
|---|---|
| Control Voltage | 100–240 VAC, 1-phase, +10%, –15% |
| Input Frequency | 50 and 60 Hz |
| Repetitive Peak Inverse Voltage Rating | 1400V (200–480V line) or 1600V (200–600V line) |
| Operating Temperature | 0°C to +50°C |
| Storage Temperature | –40°C to +85°C |
| Relative Humidity | 5–95% non-condensing |
| Shock Rating | 30 G peak acceleration for 11 ms |
| Vibration Rating | 2.5 G for 60 minutes |
| Altitude | 2000 meters without derating |
| Auxiliary Contact Rating (N.O.) | 470 VA sealed, 4700 VA inrush, 240V max., 24V min. |
| Auxiliary Contact Rating (N.C.) | 275 VA sealed, 2750 VA inrush, 240V max., 24V min. |
| Soft Start Time | 2 to 30 seconds |
| Initial Torque | 5 to 90% locked rotor torque |
| Kickstart | 500% current for 0.4 to 2 seconds |
| Current Limit | 50 to 500% full load amperes |
The control voltage is 100–240 VAC, 1-phase, 50/60 Hz with +10%, –15% tolerance.
Soft start time can be adjusted from 2 to 30 seconds.
The operating temperature range is 0°C to +50°C.
Normally open contacts rated 470 VA sealed, 4700 VA inrush, 240V max., 24V min.; normally closed contacts rated 275 VA sealed, 2750 VA inrush, 240V max., 24V min.