This guide is tailored to panel designers who wish to optimize surge protection in panels for industrial power distribution systems and equipment. It will teach panel designers how the correct size of SPD is determined for each of the seven most common types of systems.
This Littelfuse guide helps panel designers optimize surge protection in panels for industrial power distribution systems and equipment. It explains how to determine the correct SPD size for seven common system types and covers UL-required SPD markings such as Type 1, Type 2, and Type 3 classifications.
The document describes SPD classifications under UL 1449, modes of protection using metal oxide varistors (MOVs), and characteristics of good surge protection such as compact size, high SCCR, pluggable modules, thermal protection, and remote contacts. It also discusses the transition from NEMA-style to DIN-rail mountable SPDs.
| Nominal Discharge Current test levels | 3 kA, 5 kA, 10 kA, and 20 kA |
|---|---|
| VPR test combination waveform | 6 kV, 3 kA 8/20 |
| MCOV above nominal voltage | 15 to 25 % |
| Type 3 maximum distance from panel | 10 meters (30 feet) |
| IP rating finger-safe protection | solid objects up to 12 mm |
| Nominal interrupting rating | 20 kA |
Type 1, Type 2, and Type 3 SPDs.
A minimum of 10 meters (30 feet).
Thickness determines clamping ability; diameter determines surge capacity.
Space, and it is less expensive and easier to work with.