This manual describes installation, wiring, and other tasks required to make the controller ready for operation.
The Yokogawa UT551 is a digital indicating controller designed for single-loop control. This installation and wiring manual provides instructions for mounting, wiring, and hardware specifications to prepare the controller for operation.
The manual covers safety precautions, model and suffix codes, installation procedures including panel cutout dimensions and mounting bracket tightening torque, wiring guidelines for power supply, thermocouple, RTD, and control outputs, and detailed hardware specifications for retransmission output, current output, voltage pulse output, and relay contact output. Terminal wiring diagrams are provided for various model configurations.
| Retransmission output count | 1 or 2 |
|---|---|
| Retransmission output signal | 4-20, 0-20, 20-4, or 20-0 mA DC |
| Retransmission output accuracy | ±0.1% of span (±5% for ≤1 mA) |
| Control output current signal | 4-20, 0-20, 20-4, or 20-0 mA DC |
| Control output accuracy | ±0.1% of span (±5% for ≤1 mA) |
| Voltage pulse on-voltage | 12 V or more (load ≥600 Ω) |
| Voltage pulse resolution | 10 ms or 0.1% of output |
| Relay contact resolution | 10 ms or 0.1% of output |
| Power supply type | Single-phase instrument power supply |
| Loop power supply options | 15 VDC or 24 VDC |
Install the controller at an angle within 30° from horizontal with the front panel facing upward. Do not install it facing downward, and keep the right and left sides horizontal.
Turn off the power to the controller before installing it on the panel because there is a possibility of electric shock. Wiring must be carried out by personnel who have basic electrical knowledge and practical experience.
The controller should be installed where temperature can be maintained at about 23°C and the fluctuation is minimal. Never place it directly on flammable items or equipment.