This manual is the user manual for TVL series display controller. It mainly introduces the safety requirements, installation, operation and other information of the product. Please read this manual carefully to ensure the correct use of the product.
This user manual describes the TVL Series Level Process Display / Controller (referred to in the text as the TruVu meter) from Icon Process Controls. It covers basic safety requirements, general characteristics, technical data, device installation and unpacking, with a note that the manual is published at www.levelprosales.com.
The device has one current input 0-20/4-20 mA and one voltage input 0-5/1-5/0-10/2-10 V, selected in software, a 4-digit LED display with values from -999 to 9999 plus decimal point, up to two relay or OC outputs, an RS-485/Modbus RTU interface and a sensor supply output. It can be ordered in three power supply versions and uses an IR sensor under a transparent cover so presets can be changed without opening it. The extracted text also includes pages from a Level Pro Sensors manual on heavy duty industrial level transmitters.
| Current input | 0÷20 mA, 4÷20 mA, overload protected, max input current about 40 mA |
|---|---|
| Voltage input | 0÷5 V, 1÷5 V, 0÷10 V, 2÷10 V |
| Display range | -999 ÷ 9999, plus decimal point |
| Display | LED, 4 digit, 20 mm height, red or green |
| Communication interface | RS 485, 8N1 and 8N2, Modbus RTU, not separated |
| Protection level | IP 65 NEMA 4X |
| Operating temperature | -25°C to +50°C (depending on version) |
| Humidity | 5 to 90% no condensation |
| Outputs | relay 0 or 2 NO, 1A/250V AC, or 4 NO |
| Power consumption | max. 2.6 VA @ 230V AC and @ 110V AC, max. 4.5 W @ 24V DC |
| Housing material | Poly Carbonate, IP 65 NEMA 4X |
It has one current input 0-20/4-20 mA and one voltage input 0-5/1-5/0-10/2-10 V; the active input is selected by software.
An IR sensor on the front allows presets to be changed without opening the transparent cover, using an optional remote controller.
230V AC ±10%, 110V AC ±5%, 24V AC ±5% or 24V DC ±15%, depending on version.