HOERBIGER EVN 3.0H and EVN 3.0H NC Explosion Relief Valve Operation Manual

The document is an operation manual for explosion relief valves of type EVN 3.0H and EVN 3.0H NC, which are used in hygiene applications


HOERBIGER EVN 3.0H and EVN 3.0H NC Explosion Relief Valve Operation Manual - cover page
Brand
HOERBIGER
Category
Other
Document type
User Manual
Language
English
Pages
31
File format
PDF
File size
1.7 MB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
EBF70DE90B77DBFA7637087CECF266FB

About this manual

This operation manual, version 1.01, covers the HOERBIGER explosion relief valves of type EVN 3.0H and EVN 3.0H NC in sizes 266, 320, 420, 480, 565, 645 and 735, for the application "hygiene: dust explosions". The document states the EC type examination certificate FTZU 11 ATEX 0234X and names HOERBIGER Wien GmbH in Vienna as manufacturer.

The EVN 3.0H is described as an automatic re-closing venting device whose valve plate closes as soon as the pressure falls below the opening pressure, while the EVN 3.0H NC is a manual re-closing device that stays open until the valve plate is released by hand. The manual covers design and design limits (dust properties, operating temperatures, maximum protected volume, efficiency), operation, mounting of valve and sensor, safety distance, regular inspection, maintenance after an explosion, marking and examples for the counter flange.

What's inside

  • Introduction
  • Design of Explosion Relief Valve
  • Design limits
  • Operation
  • Mounting instructions
  • Influence on the surrounding
  • Regular inspection
  • Inspection and maintenance after an explosion
  • Maintenance
  • Examples for the counter flange

Specifications

Maximum KSt value300 bar * m / s
Maximum reduced explosion overpressure Pred,maxmax. 2,0 bar overpressure
Operating pressure0,2-1,0 bar absolute pressure
Static opening pressure0,05 bar +/- 20%
Maximum operation temperature180°C
Surrounding temperature-20°C to 80°C
Maximum protected net vessel volume24 m³
Valve sizes covered266, 320, 420, 480, 565, 645, 735
Efficiency value definitionEF [%] = Ae/Ag

Frequently asked questions

What is the difference between the EVN 3.0H and the EVN 3.0H NC?

The EVN 3.0H is an automatic re-closing venting device whose valve plate closes when the pressure falls below the opening pressure, while the EVN 3.0H NC opens and remains open until the valve plate is released by hand.

Which dusts were the explosion relief valves tested for?

They were tested according to EN 16009 for starches, plastics/resins/toners/sugar (melting dusts), wood/MDF/flock/cellulose (fibrous dusts), and coal and peat. They were not tested for use with metallic dusts.

What is the maximum vessel volume that can be protected by one valve?

The maximum protected volume per valve depends on the valve size, from 1,60 m³ for size 266 up to 6,00 m³ for size 735; the maximum net vessel volume that can be protected is 24 m³.

What is the static opening pressure of the valve?

The static opening pressure is 0,05 bar +/- 20%.