The document is an operation manual for explosion relief valves of type EVN 3.0H and EVN 3.0H NC, which are used in hygiene applications
This operation manual, version 1.01, covers the HOERBIGER explosion relief valves of type EVN 3.0H and EVN 3.0H NC in sizes 266, 320, 420, 480, 565, 645 and 735, for the application "hygiene: dust explosions". The document states the EC type examination certificate FTZU 11 ATEX 0234X and names HOERBIGER Wien GmbH in Vienna as manufacturer.
The EVN 3.0H is described as an automatic re-closing venting device whose valve plate closes as soon as the pressure falls below the opening pressure, while the EVN 3.0H NC is a manual re-closing device that stays open until the valve plate is released by hand. The manual covers design and design limits (dust properties, operating temperatures, maximum protected volume, efficiency), operation, mounting of valve and sensor, safety distance, regular inspection, maintenance after an explosion, marking and examples for the counter flange.
| Maximum KSt value | 300 bar * m / s |
|---|---|
| Maximum reduced explosion overpressure Pred,max | max. 2,0 bar overpressure |
| Operating pressure | 0,2-1,0 bar absolute pressure |
| Static opening pressure | 0,05 bar +/- 20% |
| Maximum operation temperature | 180°C |
| Surrounding temperature | -20°C to 80°C |
| Maximum protected net vessel volume | 24 m³ |
| Valve sizes covered | 266, 320, 420, 480, 565, 645, 735 |
| Efficiency value definition | EF [%] = Ae/Ag |
The EVN 3.0H is an automatic re-closing venting device whose valve plate closes when the pressure falls below the opening pressure, while the EVN 3.0H NC opens and remains open until the valve plate is released by hand.
They were tested according to EN 16009 for starches, plastics/resins/toners/sugar (melting dusts), wood/MDF/flock/cellulose (fibrous dusts), and coal and peat. They were not tested for use with metallic dusts.
The maximum protected volume per valve depends on the valve size, from 1,60 m³ for size 266 up to 6,00 m³ for size 735; the maximum net vessel volume that can be protected is 24 m³.
The static opening pressure is 0,05 bar +/- 20%.