Bachmann FM221 FM222 FS221/N FS222/N FASTBUS Module Product Leaflet

This document describes the features of FM221, FM222, FS221/N and FS222/N FASTBUS modules, which enable distribution of substations over long distances with a very low signal delay


Bachmann FM221 FM222 FS221/N FS222/N FASTBUS Module Product Leaflet - cover page
Brand
Bachmann
Category
Automation control Equipment
Document type
Product Leaflet
Language
English
Pages
3
File format
PDF
File size
168 KB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
9708619AD7338FF8AB8B761C72A14BAB

About this manual

Bachmann's FM221, FM222, FS221/N and FS222/N are FASTBUS modules for distributing substations over long distances with very low signal delay. The FM221 and FM222 are master modules with one or two FO interfaces; the FS221/N and FS222/N slave modules include an integrated power supply that can supply the I/O modules of a substation.

The modules support up to 15 distributed substations and connection through an LC patch cable or a Harting PushPull connector using an adapter. Multimode cable supports distances to 2000 m, and ColdClimate models are listed. The leaflet also provides order codes, accessories, cable recommendations and specifications for the Fx220 Series FASTBUS interface.

What's inside

  • FASTBUS Modules
  • Fx220 Series FASTBUS interface
  • Integrated power supply
  • Approvals / Certificates
  • Ambient conditions
  • Accessories
  • Order Codes
  • Cable Recommendations

Specifications

Line length between stations2000 m
Total lengthMax. 2300 m
Transmission mediumMultimode fiber (50/125 μm and 62.5/125 µm), max. 2000 m
FOC connector typeLC
FOC guide wavelength1310 nm
Number of stationsMax. 16 (max. 10 per line)
Link budget> 8 dB (3 dB reserve)
Input voltage24 VDC (18 to 34 V)
Nominal power (output)18.25 W
Operating temperature-30 to +60 °C
ApprovalsCE, cULus, CCC

Frequently asked questions

What is the maximum distance between FASTBUS stations?

The line length is 2000 m between stations and the total length is max. 2300 m.

What is the input voltage of the integrated power supply?

The integrated power supply input voltage is 24 VDC (18 to 34 V).

How many stations can a FASTBUS interface support?

The specification lists max. 16 stations, with max. 10 per line.

What fiber optic connector type do the modules use?

The FOC connector type is LC.

Download PDF (168 KB)