This document is a manual for Fike control panel and addressable audible module. It introduces the compatibility between the standard polarity reversal notification appliances rated 16-33V DC and Fike panel, and also lists some 120VAC devices, which are not suitable for Fike NAC circuit, need to be powered by 120VAC circuit and monitored accordingly.
This document lists compatible notification appliances and releasing devices for Fike control panels. It covers devices from manufacturers like WheeLock and Gentex, detailing their models, ratings, and compatibility requirements. Devices are categorized by type (strobe, horn, etc.) and include specifications for voltage, current, and mounting options. Some devices require specific wiring or power sources, and compatibility may depend on the control panel’s output type and jurisdictional requirements.
| Maximum Current per Circuit | 2.0 amps (24V DC) |
|---|---|
| Voltage Range | 16-33V DC |
Fike control panels are designed to be compatible with standard polarity reversal notification appliances rated 16-33V DC.
No, strobe circuits require continuous power and should never be supplied with a modulated output.
Most Fike control panel notification outputs and the addressable module outputs are both rated at 2.0 amps (24V DC) maximum per circuit.