This is a product manual for a manual actuator, which details the product's use, installation, operation, testing, and maintenance methods.
The Fike 06-152 Manual Actuator is a self-contained apparatus designed to fire up to six Gas Cartridge Actuators (GCAs) wired in series for releasing clean agent fire suppression systems. It satisfies NFPA 2001 requirements and can operate in a stand-alone mode or in conjunction with a releasing panel. The device internally generates sufficient power to activate the GCAs without requiring external electrical power for the firing circuit, though external power is used for supervision.
| Max GCA Circuit Resistance | 10 ohms |
|---|---|
| Max GCAs Fired | 6 |
| Dimensions | 10.25" tall X 6.25" wide X 3.25" deep |
| Supervision Power | 24 Volt DC |
The Manual Actuator can fire up to six GCAs wired in series.
No, it internally generates sufficient power to activate up to six GCAs without using external electrical power.
The total GCA circuit resistance, including field wiring and GCAs, must not exceed 10 ohms.