This manual contains instructions on how to use the PES-106 Eddy Current Proximity Sensor. It includes safety information, safety precautions, installation instructions, operating instructions, maintenance instructions, and troubleshooting information.
This manual provides instructions for operating and installing the PES-106 eddy current proximity sensor, including connecting it to a 24VDC power supply and signal cable, assessing sensitivity with a target material, and positioning the sensor. It also includes safety precautions and guidelines for proper installation to avoid mechanical damage or ground loops. Calibration and configuration using ZOOM software are covered for accurate measurements.
The sensor measures relative vibration and displacement using a metallic target, with a 0 to 6 mm range, and outputs 4-20 mA or 0-10 V signals via an M12 connector. Installation requires trained personnel and adherence to safety guidelines to ensure safe and accurate operation.
| Measuring Range | 0 to 6 mm / 0 to 236 mils |
|---|---|
| Output Signal | 4-20 mA or 0-10 V |
| Maximum Cable Length (Current Output) | 300 m / 984 ft |
| Maximum Cable Length (Voltage Output) | 100 m / 328 ft |
The PES-106 covers a 0 to 6 mm / 0 to 236 mils measuring range.
The PES-106 sensor must be connected to a 24VDC power supply and a receiving instrument with a signal cable and M12 connector.
The maximum extension cable length for current output is 300 m / 984 ft.
Contact VibroSystM to complete the commissioning after Section 2.2 (Assessing the actual sensitivity).