This manual provides installation, operating, and maintenance instructions for the BT Series electric boilers manufactured by Allied Engineering Company. The boilers are designed for hydronic heating applications with power ratings from 6 kW to 54 kW and operate on single or three-phase power supplies ranging from 208 Vac to 600 Vac. The unit features a BiTronic Control System that manages water temperature in three stages to ensure stability and efficiency.
| Power Rating Range | 6 kW to 54 kW |
|---|---|
| Voltage Range | 208 Vac to 600 Vac |
| Maximum Operating Pressure | 90 p.s.i. |
| Maximum Operating Water Temperature | 210°F |
| Water Capacity | 6.6 US Gallons |
| Inlet and Outlet Pipe Size | 1 1/4" NPT |
The maximum operating pressure is 90 p.s.i.
The maximum operating water temperature is 210°F.
No, the boiler is intended for indoor installation only and must not be subjected to water spray or leakage.
The minimum required clearance for the front is 12 inches for electrical components and fuses.