ICT2 Level Indicator Controller and Transmitter
This manual guides users through configuring and calibrating the ICT2 Level Indicator Controller and Transmitter. It covers relay settings, failsafe operation, calibration procedures, and 4-20mA output adjustment using a multimeter. The device translates capacitance changes into level percentages and outputs a 4-20mA signal for level monitoring.
The front panel includes buttons for menu navigation and displays level status, relay states, and calibration values. Calibration requires setting low and high level points using actual tank levels, and the device can be trimmed for accurate 4mA and 20mA output using a multimeter.
| Output Signal | 4-20mA |
|---|---|
| Power Supply | Isolated 80 to 260 VAC 50/60 Hz |
| Relay Configuration | Up to 4 relays (Rly1-Rly4) |
| Calibration Method | Wet-calibration using capacitance to level translation |
Press the CALIB menu, then select CL LO. Set the actual level percentage using the Up/Down buttons and confirm with Enter.
Failsafe operation defines how the level is converted to Alarm or Normal. High failsafe triggers alarm at or above the high switching point; Low failsafe triggers alarm at or below the low switching point.