This manual introduces the use of the 5500 flow monitor, including power connections, sensor connections, pulse output connections, etc.
This manual provides step-by-step instructions for connecting power, sensors, and outputs for the +GF+ SIGNET 5500 Flow Monitor. It covers wiring for sensor pulse outputs, auxiliary outputs, 4-20 mA current outputs, relay controls, and totalizer reset. The document also explains menu navigation and output configuration options for alarm, pulse, and totalizer modes.
Technical notes address noise reduction, voltage compatibility, and relay contact ratings to ensure safe and accurate operation.
| Power Supply | 12 - 24 VDC or 12 - 24 VAC |
|---|---|
| Maximum Relay Contact Ratings | 5 A @ 30 VDC, 5 A @ 125 VAC, or 3 A @ 250 VAC |
| 4-20 mA Output Loop Impedance | 350 Ω with 12 V supply, 950 Ω with 24 V supply |
The SIGNET 5500 accepts 12 to 24 volts DC or 12 to 24 volts AC.
The maximum loop impedance is 350 Ω with a 12 V supply and 950 Ω with a 24 V supply.
Relay contacts are rated at 5 A @ 30 VDC, 5 A @ 125 VAC, or 3 A @ 250 VAC.