This manual introduces the Klay Instruments B.V. 8000 series pressure and level transmitters, including the 8000-SAN and 8000 models, as well as their features and characteristics and their uses.
This manual provides instructions for the Klay Instruments SERIES 8000 and SERIES 8000-SAN solid-state pressure and level transmitters. These devices utilize a bridge resistive silicon sensor with a stainless steel foot and flush diaphragm to measure pressure in industrial processes, converting the signal to a 4-20 mA output.
| Output Signal | 4 - 20 mA |
|---|---|
| Sensor Type | Bridge resistive silicon sensor |
| Wetted Parts Material (Standard) | SS 316 |
| Operating Temperature Range | -30° C < Tamb < 70° C |
| Minimum Power Supply (Local Indicator) | 15.5 Vdc |
| Hazardous Area Voltage Limit | 13 – 26,5 Vdc |
Set output to 4 mA, apply air pressure, set output to 20 mA, remove pressure, check output is 4 mA, install transmitter, and set output to 4 mA based on mounting position.
Yes, the SERIES 8000 and 8000-SAN are certified for applications in hazardous areas with specific ATEX and IECEx ratings.
Mounting vertically causes a zero shift; if mounted up, the shift is less than 4 mA, and if mounted down, the shift is greater than 4 mA.