This user manual provides detailed instructions for installing, operating, and maintaining the VMX-agility series soft starters. It includes safety warnings, mounting guidelines, electrical specifications, and control terminal configurations. The manual also covers environmental ratings, derating for altitude and temperature, and accessory installation. It is intended for qualified personnel and includes technical details for integration into industrial systems.

The document is structured to guide users through setup procedures, including auto setup and advanced parameter settings. It also explains communication protocols like Modbus RTU, fault codes, and troubleshooting. Safety precautions and compliance with local electrical codes are emphasized throughout.

What's inside

  • Safety
  • Installation
  • Mounting
  • Enclosure Ventilation
  • Altitude Derate
  • Handling
  • Accessories
  • Dimensions
  • Environmental Specifications
  • Horizontal Mounting

Specifications

Ambient Operating Temperature-20°C to 40°C; above 40°C derate linearly by 2% per °C to a maximum of 60°C
Maximum Altitude1,000m (3281ft); above 1000m derate by 1% per 100m (328ft) to a maximum of 2,000m (6562ft)
Environmental RatingMain Circuit: IP00 (IP20 with optional finger guards); Control Circuit: IP20
Weight (Frame Size 1)1.97kg (3.75lb)
Weight (Frame Size 2)6kg (13.22lb)

Frequently asked questions

What is the IP rating for the main and control circuits?

Main circuit: IP00 (IP20 with optional finger guards); Control circuit: IP20.

What is the maximum altitude at which the VMX-agility can be used without derating?

Above 1000m, derate by 1% per 100m up to a maximum of 2000m.

What is the ambient operating temperature range for the VMX-agility?

From -20°C to 40°C; above 40°C, derate linearly by 2% per °C up to 60°C.