This is a manual addendum for VMX-B configured softstart packages.
This addendum provides operational instructions for VMX-B softstart packages, including line voltage adjustment, power connections, remote start/stop control, and run status output contacts. It also details programming instructions for motor FLA and service factor, fault codes, and parameter settings. The document is intended for use with wiring diagrams #93-3825 Rev 1 and VMX user manual.
| Line Voltage | Default 460VAC, adjustable to 230VAC or 208VAC |
|---|---|
| Remote Control | 2 or 3 wire dry contacts rated at 120VAC (0.1Amp) |
| Run Status Output Contacts | 2 Form-C (N.O and N.C.) contacts |
Move wire #1L2B from the 480V (H4) terminal to the 230V (H3) or 208V (H2) terminal.
2 or 3 wire dry contacts rated at 120VAC (0.1Amp).
Enter values using Fn # F001 for FLA and F002 for Service Factor before start attempt.