This document is the manual for the VMX-B motor soft starter. It introduces its working principle, installation method and usage method.
This manual provides instructions for configuring and operating VMX-B soft starters, including line voltage adjustment, power and remote control connections, and run status outputs. It also details programming steps for motor FLA and service factor settings, along with troubleshooting fault codes. The device supports both soft start and X-LINE modes for emergency operation, with overload relay settings based on motor nameplate data.
The manual is intended for use with wiring diagrams #93-3880 Rev B (CB/FS) or #93-3881 Rev B (MLO) and the VMX 2 user manual. It includes terminal strip configurations for remote control and run status contacts, as well as a full parameter list for customization.
| Line Voltage | 460VAC (default), adjustable to 230VAC or 208VAC |
|---|---|
| Remote Control | 2 or 3 wire dry contacts rated at 120VAC (0.1Amp) |
| Run Status Output | 2 Form-C (N.O and N.C.) contacts |
Move wire #1L2B from the 480V (H4) terminal to the 230V (H3) or 208V (H2) terminal.
The default is 460VAC, but it can be adjusted to 230VAC or 208VAC.