This manual describes the functions, configuration, and use of the Allen-Bradley Broadband Communication Interface (Cat. No. 1771-KRF/B).
This manual explains how to install and configure the 1771-KRF/B module for use with Data Highway and remote I/O networks over broadband cable systems. It details compatible devices, connection methods, channel settings, and troubleshooting using diagnostic LEDs.
The module supports 18 frequency subchannels and connects via twinaxial baseband cable to DH/DH+ or remote I/O modules and broadband coaxial cable to the network. It operates at 57.6K or 115.2K baud and is designed for industrial environments with noise immunity at RF frequencies.
| Communication Ports | DH/DH+ and remote I/O baseband: 3-screw terminal block; Broadband: female type F connector |
|---|---|
| Communication Rate | 57.6 and 115.2K baud |
| Cabling | DH/DH+ and Remote I/O port: Twinaxial Baseband Belden 9463; Broadband port: 75 ohm, RG6 coaxial |
| Power Requirement | 1.5 amps @ 5VDC |
| Ambient Temperature Rating | 32o to 140o F (0 to 60o C) operational 40o to 185o F (40o to 85o C) storage |
| Ambient Humidity Rating | 5 to 95% noncondensing |
| Frequency Channels | Channel Pair Transmit Frequency (MHz) Receive Frequency (MHz) T12 to L 35.75 to 41.75 228 to 234 T13 to M 41.75 to 47.75 234 to 240 T14 to N 47.75 to 53.75 240 to 246 |
| Subchannel Spacing | 750 KHz |
| Transmit Level | +45 dBmV (nominal) |
| Receive Level Range | 13 dBmV to +15 dBmV |
| Regulatory Compliance | FCC Class A Subpart J of part 15; UL listed when used with listed bulletin 1771 systems; Canadian DOC, Class A, RIR, September 1988 |
The KRF operates at 57.6K or 115.2K baud, depending on the modules used.
The 1771-KRF/B is compatible with various Allen-Bradley DH/DH+ and remote I/O modules, including 1771-KE/KF, 1775-KA, 1785-KA, and 1772-SD2.
The 1771-KRF/B is qualified for use with a broadband cable system with a radius of four miles.