This manual describes the settings parameters of HMS-1655 Fume Hood Controller
This document provides installation instructions for the Triatek HMS-1655 Fume Hood Controller. It details the electrical requirements, including power supply specifications and communication protocols like BACnet MS/TP and Metasys N2. The guide also covers mechanical mounting dimensions and wiring diagrams for various sensor inputs and actuator outputs.
| Analog Inputs | 4-20mAdc, 0-5Vdc or 0-10Vdc |
|---|---|
| Analog Outputs | 4-20mAdc, 0-5Vdc or 0-10Vdc |
| Relay Outputs | 1A@24VDC |
| Power Supply | Class 2, 24Vac ±10%, 30VA universal 120/240 to 24 Vac, 60/50 Hz |
| Display Resolution | 240 x 320 portrait |
| Operating Temperature | 32° to 125° F |
| Operating Humidity | 10% - 95% RH, Non-condensing |
| Face Velocity Accuracy | 0-200 FPM ± 2 FPM* |
The recommended cable type is Belden 1325A.
Yes, a 120/24VAC, 20Va third-party transformer can be used for the actuator, but it must be separate from the controller's transformer.