CW-5000/5200 Series Industrial Chiller Maintenance Manual

This document introduces the maintenance methods of CW-5000/5200 industrial chillers, including common faults such as red light on, no water circulation, and controller alarm codes.


CW-5000/5200 Series Industrial Chiller Maintenance Manual - cover page
Brand
CW-5000/5200 Series
Category
Industrial Supply
Document type
Service Manual
Language
English
Pages
15
File format
PDF
File size
1.5 MB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
66202E527C5FDA8EB115FBEAE5588A45

About this manual

This document serves as a maintenance and troubleshooting guide for the CW-5000/5200 Series Industrial Chiller. It details procedures for diagnosing and resolving various alarm conditions, such as water circulation failures, temperature sensor errors, and power supply issues. The guide includes specific steps for testing components like flow switches, relays, and DC pumps.

What's inside

  • Chiller Alarm with water circulation
  • Chiller Alarm without water circulation
  • Temperature Controller T-503 alarms
  • No power on the chiller
  • Alarm code E1: ultrahigh room temperature
  • Alarm code E2: ultrahigh water temperature
  • Alarm code E3: ultralow room temperature
  • Alarm code E4: room temperature sensor failure
  • Alarm code E5: Water temperature sensor failure
  • DC Pump and Switching Power Supply diagnostics

Specifications

Switching power supply operating voltageDC24V
Baffle Flow switch relay coil voltageAC220V
Hall Flow switch relay coil voltageDC24V
Minimum clearance from air inlet obstruction30cm
Minimum clearance from air outlet obstruction50cm
Compressor electric start-up capacity threshold10%

Frequently asked questions

What causes alarm code E1 (ultrahigh room temperature)?

This is caused by an ambient temperature above 40°C or poor ventilation. The chiller must be placed with at least 30cm clearance from air inlet obstructions and 50cm from air outlet obstructions.

How do I test if the flow switch is faulty?

Cut off the power wires to the flow switch and short them. If the alarm stops and the green light turns on, the flow switch has failed and needs replacement.

What is the operating voltage for the CW-5000 Series switching power supply?

The operating voltage is DC24V. If the output is lower than DC18V, it may affect the pump lift and flow.

What should I do if the chiller has no power?

First, open the safety tube to check if the fuse is fused. If the fuse is blown, replace it. Then check the power switch for voltage.

Download PDF (1.5 MB)