This document introduces the maintenance methods of CW-5000/5200 industrial chillers, including common faults such as red light on, no water circulation, and controller alarm codes.
This document serves as a maintenance and troubleshooting guide for the CW-5000/5200 Series Industrial Chiller. It details procedures for diagnosing and resolving various alarm conditions, such as water circulation failures, temperature sensor errors, and power supply issues. The guide includes specific steps for testing components like flow switches, relays, and DC pumps.
| Switching power supply operating voltage | DC24V |
|---|---|
| Baffle Flow switch relay coil voltage | AC220V |
| Hall Flow switch relay coil voltage | DC24V |
| Minimum clearance from air inlet obstruction | 30cm |
| Minimum clearance from air outlet obstruction | 50cm |
| Compressor electric start-up capacity threshold | 10% |
This is caused by an ambient temperature above 40°C or poor ventilation. The chiller must be placed with at least 30cm clearance from air inlet obstructions and 50cm from air outlet obstructions.
Cut off the power wires to the flow switch and short them. If the alarm stops and the green light turns on, the flow switch has failed and needs replacement.
The operating voltage is DC24V. If the output is lower than DC18V, it may affect the pump lift and flow.
First, open the safety tube to check if the fuse is fused. If the fuse is blown, replace it. Then check the power switch for voltage.