Featured CW-5000/5200 Series manuals

CW-5000/5200 Series Industrial Chiller Maintenance Manual
This document serves as a maintenance and troubleshooting guide for the CW-5000/5200 Series Industrial Chiller. It details procedures for diagnosing and resolving various alarm conditions, such as water circulation failures, temperature sensor errors, and power supply issues. The guide includes specific steps for testing components like flow switches, relays, and DC pumps.
Covers: Chiller Alarm with water circulation · Chiller Alarm without water circulation · Temperature Controller T-503 alarms · No power on the chiller · Alarm code E1: ultrahigh room temperature · Alarm code E2: ultrahigh water temperature
Latest CW-5000/5200 Series manuals
CW-5000/5200 Series Industrial Chiller Maintenance Manual
Service Manual 15 pages · 1.5 MB · ENThis manual provides troubleshooting and repair instructions for CW-5000/5200 Series industrial chillers, covering alarm codes, power issues, and component…
Which document do I need?
Service Manual
Disassembly, diagnostics and part numbers, for repair.
Questions answered in CW-5000/5200 Series manuals
What causes alarm code E1 (ultrahigh room temperature)?
This is caused by an ambient temperature above 40°C or poor ventilation. The chiller must be placed with at least 30cm clearance from air inlet obstructions and 50cm from air outlet obstructions.
From: CW-5000/5200 Series Industrial Chiller Maintenance Manual
How do I test if the flow switch is faulty?
Cut off the power wires to the flow switch and short them. If the alarm stops and the green light turns on, the flow switch has failed and needs replacement.
From: CW-5000/5200 Series Industrial Chiller Maintenance Manual