Gamewell-FCI 7100 Driver Manual

This manual describes the functionality, scope and usage of the Gamewell-FCI 7100 Series driver.


Gamewell-FCI 7100 Driver Manual - cover page
Brand
Gamewell-FCI
Document type
User Manual
Language
English
Pages
20
File format
PDF
File size
676 KB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
88ADC035F16188ABAB76BDFF7E65DE4C

About this manual

This manual provides instructions for configuring and using the Gamewell-FCI 7100 driver with FieldServer systems. It details hardware connections, data array setup, and client-side configuration parameters for communication with FCI 7100 panels. The driver supports passive message reception and storage, with options for event filtering and node-specific data handling.

The document includes sections on applicable hardware, communication board pinouts, data array formats, and map descriptor configurations. It also covers troubleshooting and driver-specific features such as panel synchronization and event processing for different firmware versions.

What's inside

  • Description
  • Driver Scope of Supply
  • Hardware Connections
  • Data Array Parameters
  • Client Side Configuration
  • Useful Features
  • Troubleshooting
  • Reference

Specifications

Max Nodes Supported (Client)1 Node per serial port
Max Nodes Supported (Server)32 Nodes
Baud Rate1200
Data Array FormatsFloat, Bit, Byte, Uint16, Uint32, Sint16, Sint32

Frequently asked questions

What is the driver’s role in communicating with the FCI 7100 panel?

The driver is a passive client that receives and stores messages from the 7100 panel but does not poll for data or send commands. It processes messages for firmware versions 2.20 and later, requiring a 20-character System ID for 3-line messages.

How do I configure multiple panels in a networked setup?

Set the local panel’s Node_ID to zero and create separate Node descriptors for each panel, assigning each a unique Node_ID. Use the 'Reset_by_any_Node' or 'Reset_by_this_Node_Only' option to control reset behavior.

What data formats are supported in Data Arrays?

Supported formats include Float, Bit, Byte, Uint16, Uint32, Sint16, and Sint32. Each Data Array can only use one format.

Download PDF (676 KB)