Describes how to use energy recovery ventilators
This manual provides step-by-step instructions for installing Fantech Energy Recovery Ventilators (models SER 6004, SER 9504, SER 13004). It covers location requirements, duct connection methods, airflow balancing, and system integration with HVAC equipment. Safety warnings and code compliance are emphasized, including compatibility with combustion equipment and condensate drainage.
The guide includes diagrams for different installation configurations: fully dedicated, partially dedicated (direct and indirect connections), and simplified setups. It also details weatherhood installation, duct sealing, and airflow measurement procedures to ensure proper system performance.
The weatherhoods must have built-in screens with a 1/4 inch (6.35 mm) minimum mesh to prevent birds and rodents from entering the ductwork.
All ducts connecting the ERV to weatherhoods should use insulation with a minimum R value of 4 (RSI 0.75).
During airflow balancing, a deviation of 10% or less between the exhaust air leaving the system and the supply air entering the system is acceptable.