This manual describes the objectives, contents, and implementation steps of the oil and grease management program, and provides related requirements for design, installation, and maintenance of grease interceptors for food service facilities.
This document serves as a supplement to Ordinance No. 030278, establishing an oil and grease management program for the City of Gainesville, doing business as Gainesville Regional Utilities (GRU). The primary objective is to eliminate sewer system overflows and reduce pollution by controlling discharges from food service facilities.
The minimum capacity for any grease interceptor is 1000 gallons.
Grease interceptors must be pumped out completely at a minimum frequency of monthly.
There must be a minimum period of three weeks between each required pumping.