《DIGITAL Geothermal Heat Pumps TE/TZ/TES/TEP 97B0601N01 Rev.: 3/10/15 Tranquility® Digital (DXM2) Troubleshooting Guide》 is a maintenance manual that provides troubleshooting methods for this model of geothermal heat pump.
This document serves as a troubleshooting guide for ClimateMaster Tranquility Digital Packaged Heat Pumps equipped with the DXM2 control board. It emphasizes that most service problems relate to water flow rather than refrigerant issues and can often be addressed without refrigerant gauges. The guide recommends using the ATC32 communicating thermostat or ACDUO2 service tool for diagnostics.
| Voltage Range | 197-254V |
|---|---|
| DC Voltage Range (Pump Off) | 0.5-10 VDC |
| DC Voltage Range (Valve) | 3.3-10VDC |
You must have the ATC32 communicating thermostat or the ACDUO2 communicating service tool to properly work on these units.
No, installing gauges on packaged heat pumps can do more harm than good because they contain less refrigerant compared to split systems.
The control defaults are 7° heating and 10° cooling.