This document describes how to troubleshoot water source heat pumps that are not operating
This manual provides step-by-step troubleshooting procedures for ClimateMaster water source heat pumps. It includes instructions for retrieving fault codes using CXM, DXM, and DXM2 controllers, performing water flow diagnostics, and checking mechanical components like compressors and blowers. Safety warnings are included for electrical and refrigerant handling. The document also outlines precautions for installation and winter operation to prevent damage.
The guide is intended for technicians and covers both operational and non-operational scenarios, with detailed fault code charts and diagnostic steps for each component. It emphasizes compliance with local codes and the need for certified technicians for refrigerant service.
Momentarily short the test terminals near the dip switches to enter Test Mode. The Status LED will flash a code representing the last fault. Count the flashes between ten-second pauses and compare to the fault code chart.
Do not restart the unit without inspecting and remedying the faulting condition. Equipment damage may occur.
Check for lockout conditions, verify voltage and amperage within 10% of data plate rating, check windings for open or shorted circuits, verify contactor engagement, and check wiring for burnt or loose connections.