Introduces the characteristics and features of the WCT400/410 series cooling tower conductivity controller
The Walchem WCT400 Series controllers offer conductivity and watermeter-based control of cooling tower water, control of corrosion/scale inhibitor feed, and with the WCT410 models, control of two biocide pumps. The controllers are microprocessor driven industrial type with on/off control outputs. A timed sample mode may be selected, and on small towers can reduce installation costs by eliminating the need for a sampling bypass line. An optional isolated 4-20 mA output that is proportional to the conductivity reading is available for all models. Any set point may be viewed without interrupting control. Each set point change will take effect as soon as it is entered. An access code is available to protect set point parameters, while still allowing settings to be viewed. The model WCT410 biocide outputs are scheduled on a user selectable 1, 2, or 4 week cycle. Each biocide output is independent and may be programmed for one add per day. (in 1, 2 or 4 week cycle) or up to 10 times per day (in daily cycle). It is possible to add both chemicals in the same day, however, as a safeguard they will not occur at the same time. Biocide outputs may use independent pre-bleeds and lockout times. All outputs are interlocked with a flow switch input. An alarm relay is provided with WCT410 models. It is triggered by: Low Conductivity reading High Conductivity reading No Flow situation Bleed Timeout Sensor Error Temp Error. Our unique USB feature provides the ability to upgrade the software in the controller to the latest version. An advanced USB capability option is available. The Config file feature allows you to save all the set points from a controller onto a USB flash disk, and then import them into another controller, making the programming of multiple controllers fast and easy. The data logging feature allows you to save the last 2 month's readings and events to a USB flash disk.
| Conductivity Range | 0 - 10,000 µS/cm |
|---|---|
| Conductivity Resolution | 1 µS/cm |
| Conductivity Accuracy | 10 - 10,000 µS/cm ±1% of reading |
| Temperature Range | 32 - 158°F (0 - 70°C) |
| Input Power | 100-240 VAC, 50/60 Hz, 8A |
| Enclosure Material | Polycarbonate |
| NEMA Rating | NEMA 4X |
| Dimensions | 8.5" x 6.5" x 5.5" |
The conductivity range is 0 - 10,000 µS/cm.
The alarm relay is triggered by Low Conductivity reading, High Conductivity reading, No Flow situation, Bleed Timeout, Sensor Error, or Temp Error.
Yes, the unique USB feature provides the ability to upgrade the software in the controller to the latest version.