E+E EE160 Humidity and Temperature Transmitter HVAC User Manual

This is a user manual of EE160 temperature and humidity transmitter, which includes installation, usage and maintenance


E+E EE160 Humidity and Temperature Transmitter HVAC User Manual - cover page
Brand
E+E
Document type
User Manual
Language
English
Pages
5
File format
PDF
File size
1.5 MB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
0522A34870479C9469BE758DAAA47B56

About this manual

This user manual provides instructions for installing, operating, and maintaining the E+E EE160 humidity and temperature transmitter in HVAC applications. It includes details on mounting, wiring, LED indicators, configuration via RS485, and calibration. The device supports Modbus RTU and BACnet MS/TP protocols with configurable addresses and output scaling. Maintenance involves cleaning the sensing head and replacing the filter cap in polluted environments. The manual also covers technical specifications, power requirements, and safety precautions.

What's inside

  • Installation and Mounting
  • LED Indicators
  • RS485 Configuration
  • Modbus RTU Setup
  • BACnet Setup
  • Technical Specifications
  • Maintenance and Cleaning
  • Calibration and Adjustment
  • Safety Precautions

Specifications

Operating Temperature-40...60 °C (-40...140 °F)
Storage Temperature-20...60 °C (-4...140 °F)
Humidity Sensor Accuracy±2.5 % RH at 20 °C
Temperature Sensor Accuracy±0.3 °C at 20 °C
Output Options4-20 mA, 0-10 V, RS485 (Modbus RTU or BACnet MS/TP)
Power Supply15-35V DC or 24V AC ±20% for 4-20 mA; 10V + RL x 20 mA < UV < 35V DC
Housing MaterialPolycarbonate, UL94V-0 approved
Protection ClassIP65 / NEMA 4
Cable GlandM16 x 1.5
Typical Current Consumption4-20 mA output: 24V DC max. 40 mA; 0-10 V output: 5 mA; RS485 output: 5 mA

Frequently asked questions

What is the operating temperature range for the EE160?

The operating temperature range is -40 to 60 °C (-40 to 140 °F).

How accurate is the humidity measurement at 20°C?

The humidity accuracy is ±2.5% RH at 20°C.

What communication protocols does the EE160 support?

The EE160 supports Modbus RTU and BACnet MS/TP over RS485.

What is the default Modbus slave address?

The default Modbus slave address is 245.