This document is the installation and operation guide for Onicon's system 40 BTU measurement system. It mainly introduces the safety information, installation precautions, use methods and maintenance and maintenance methods of the product.
This manual serves as the installation and operation guide for the Onicon SYSTEM-40 BTU Measurement System. It details the purpose of the guide, typical installation scenarios, and standard features including transmitter and flow sensor performance specifications. The document outlines safety precautions and working environment requirements essential for proper deployment.
| Accuracy (Transmitter) | ≤ 0.09% at 30°F Δt |
|---|---|
| Accuracy (Flow Sensor) | ±1% of reading over 25:1 turndown |
| Operating Temperature | -13°F to 131°F |
| Input Power | 20-28V AC/DC, 5 VA maximum |
| Maximum Operating Pressure | 400 psi |
| Serial Communication Baud Rates | 4800, 9600, 19200, 38400, 76800, or 115200 |
Only qualified service personnel should attempt to install or service this product.
The system meets EN1434 Class 1 requirements with a minimum Δt of 3K.
Options include two auxiliary pulsed inputs and one pulsed output, or one pulsed input, one pulsed output, and one analog output.