This is the installation and operation manual for the ONICON F-3500 electromagnetic flow meter.
This manual serves as a reference tool for the installation, operation, and maintenance of the ONICON F-3500 Insertion Electromagnetic Flow Meter. It covers safety precautions, unpacking procedures, and detailed installation steps for both standard and hot tap configurations. The guide also explains the meter's operating principles based on Faraday's Law and provides instructions for wiring connections and startup commissioning.
| Accuracy | ± 1.0% of reading from 2 to 20 ft/sec |
|---|---|
| Pipe Size Range | Standard: 3-72" nominal; Small Pipe: 1¼-2½" nominal |
| Input Power | 20 - 28 VAC 50/60Hz, 250 mA maximum |
| Liquid Temperature Range | 15° to 250° F |
| Operating Pressure | 400 PSI maximum |
| Materials of Construction | Wetted metal components - 316L stainless steel |
| Output Signal | Analog output (Isolated), selectable 4-20 mA, 0-10 V or 0-5 V |
Persons must have complete knowledge of their trade skills and be competent to work on high pressure hot and cold water and steam systems.
Yes, using a 'Hot tap' installation kit and a 1 inch wet tap drill to access the pipe while the system is operating.
Grounding rings are required before and after the meter whenever it is installed in non-metallic or lined pipes to eliminate electrical noise.