Siemens 7PG21 Solkor Rf Feeder Protection Service Manual

This document provides the operation manual of 7PG21 Solkor Rf Feeder Protection, including usage instructions, performance specifications, application guides, settings, installation, commissioning, diagrams, etc.


Siemens 7PG21 Solkor Rf Feeder Protection Service Manual - cover page
Brand
Siemens
Document type
Service Manual
Language
English
Pages
81
File format
PDF
File size
3 MB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
CFF5F13B1D59A5E31D809809E03B287D

About this manual

This document is a technical service manual for the Siemens 7PG21 Solkor Rf Feeder Protection device. It details operation principles, performance specifications, installation procedures, commissioning steps, and wiring diagrams. The device is a pilot wire current differential protection system for 2-core pilot cables with high resistance. It includes features like high transient stability, low fault settings, and optional 15kV isolation. The manual also explains how to convert the relay to Solkor R mode and how to configure padding resistors for different pilot resistance values.

The device uses a summation transformer to compare currents at each end of a three-phase line over a single pilot pair. Operation is based on circulating current and equipotential relaying points that alternate between ends during half-cycles. The manual includes detailed schematics and explains the role of non-linear resistors, padding resistors, and diodes in voltage limiting and stability.

What's inside

  • Description of Operation
  • Performance Specification
  • Applications Guide
  • Settings
  • Installation
  • Commissioning
  • Diagrams

Specifications

Insulation Level5kV between secondary winding and primary winding
Operating ElementAttracted armature type with three contacts
Pilot ResistanceConfigurable via padding resistors
Conversion to Solkor RBy moving internal wire links and fitting an external wire link

Frequently asked questions

What is the insulation level of the Solkor Rf device?

A 5kV insulation level is provided between the secondary winding of the summation transformer and its primary winding.

How can the Solkor Rf be converted to Solkor R mode?

By moving internal wire links and fitting an external wire link.

What are the padding resistor values for Solkor Rf?

The padding resistors comprise five series connected sections, each section having a short circuiting link. The values of the resistance on the sections are 35 ohms, 65 ohms, 130 ohms, 260 ohms and 500ohms.