This manual contains information about the safe operation and maintenance of the Martindale PD440SX and PD690SX products. The manual contains the following content: meaning of symbols and markings, precautions, product inspection, product description, accessories, battery installation, operation, maintenance, warranty, etc.
This manual provides instructions for the Martindale PD440SX and PD690SX portable battery-powered proving units. These devices are designed for testing contact-type voltage detectors up to 440V and 690V, respectively. The document covers safety precautions, unit inspection, and detailed operating procedures including LED indications and testing methods for lamps, testers, and cables.
| Max Output Voltage (PD440SX) | 440V ramping to 50V |
|---|---|
| Max Output Voltage (PD690SX) | 690V ramping to 50V |
| Output Frequency | 50Hz nominal |
| Power Source | 6 x 1.5V AA alkaline batteries |
| Operating Temperature | -10°C to 40°C |
| Dimensions | 150 x 80 x 35mm |
The PD440SX is designed for testing contact type voltage detectors up to 440V.
The PD690SX is designed for testing contact type voltage detectors up to 690V.
The unit ramps output voltage down in a sequence lasting for a duration of 10s.
The unit requires 6 new 1.5V, AA alkaline batteries (IEC LR6, NEDA 15A).