This is an air conditioner controller manual that introduces the controller's functions, operation methods, and installation methods
The YR-E17 Wired Controller Operation & Installation Manual provides instructions for using the controller to adjust temperature, fan speed, timer settings, and other functions. It details the interface display parts, key functions such as energy saving and child lock, and explains how to configure the device using dip switches for various modes like fresh air units or master/slave configurations.
The document also includes specific wiring instructions for connecting the controller to indoor units. It describes three connection methods, including controlling up to 16 indoor units, and provides a table specifying wire gauge requirements based on communication wiring length to ensure proper signal transmission.
| Temperature Adjusting Accuracy | 0.5°C (1°F) |
|---|---|
| Default Cooling/Dry Temperature Limit | 23°C (74°F) |
| Default Heating Temperature Limit | 26°C (78°F) |
| Max Indoor Units Controlled | 16 sets |
In energy saving mode and temp. compensation mode, the adjusting step is 1°C (1°F) a time.
One wired controller can control a maximum of 16 sets of indoor units.
For communication wiring lengths between 300m and 400m, a 1.25mm 2 x3-core shielded wire (16AWG,3wire) is required.