Electro-Steam LG-10 through LG-40 Steam Generator User, Installation, & Maintenance Manual

This file is the user manual of the electric steam generator LG-10~LG-40 of Electro-Steam Generator Corp. It mainly introduces the working principle, safety precautions and daily maintenance of the electric steam generator


Electro-Steam LG-10 through LG-40 Steam Generator User, Installation, & Maintenance Manual - cover page
Brand
ElectroSteam
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
33
File format
PDF
File size
6.3 MB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
F593CEACAE626927EB170C862DADB568

About this manual

This document serves as the User, Installation, and Maintenance Manual for the Electro-Steam LG-Series steam generators, covering models LG-10, LG-15, LG-20, LG-25, LG-30, and LG-40. The unit is a high-pressure chamber filled with water heated by submerged resistance elements, designed to maintain preset operating pressure and water levels automatically. It complies with ASME Boiler and Pressure Vessel Code Section I.

What's inside

  • Installation Instructions
  • Operation & Sequence of Events
  • Manual Blow Down
  • Cleaning Water Level Probes
  • Cleaning or Replacing Heaters
  • Replacing Glass Gauge and Rubber Washers
  • Chamber Cleaning & Chemical Treatment
  • Pressure Control Data Sheet
  • Setting the Pressure Controls
  • Calculations & Data Sheets

Specifications

Power Range10-40kW
Ambient Temperature Limit105°F
Water Purity RequirementNOT to exceed 26,000 OHMS per CM
Water Temperature Range32°F – 140°F or 0°C – 60 °C
Water Supply Pressure Range20PSI – 150PSI
Safety Valve TypeOverpressure Safety Relief Valve

Frequently asked questions

How often should I perform a manual blow down?

In normal water areas, it should be done once a week; in bad water areas, once a day.

How frequently should water level probes be cleaned?

In normal water areas, twice a year; in bad water areas, 3-4 times a year.

What is the maximum recommended ambient temperature for the unit?

The ambient temperature around the unit must not exceed 105°F.