This document is about the safety instructions for RegO® gas valves
This manual provides operation and maintenance instructions for the Macro Technologies CryoMac3-50M and CryoMac3-50M-S LNG (Liquid Natural Gas) Fueling Nozzles. It details safety precautions regarding Liquefied Natural Gas (LNG), including the risks of asphyxiation and freeze burns, and specifies the required personal protective equipment such as full face shields and thermal gloves.
The document outlines the three handle positions (Connected, Vent, and Open) and explains the function of the Stop Assembly in releasing trapped gases. It includes step-by-step installation instructions, operating procedures for coupling and uncoupling the nozzle, and a maintenance schedule for replacing parts like the poppet assembly and interface seals.
| Fluid Compatibility | Liquid Natural Gas (LNG), Methane, Liquid Nitrogen (LIN) |
|---|---|
| Maximum Refueling Pressure | 500 PSIG / 34.5 BAR |
| Burst Pressure | > 1,500 PSIG (103.5 BAR) |
| Rated Flow | 50 GPM @ 250 PSIG (LNG) |
| Nozzle Weight | 10.4LBS |
| Port Size | 1" Male SAE 37° Flare (SAE J514) |
| Operating Temperature | -320°F to +140°F (-195°C to 60°C) |
Operators must wear a full face shield, thermal gloves approved for cryogenic use, a cryogenic smock, and solid shoes capable of withstanding cryogenic spill.
Yes, the nozzle is compatible with Liquid Nitrogen (LIN) in addition to Liquid Natural Gas (LNG) and Methane.
The maximum refueling pressure is 500 PSIG (34.5 BAR).
No, for safety reasons, the Nozzle should not be removed from the Coupling while in the Vent Position.