RegO L-545 LP-Gas Serviceman's Manual

provide relevant LP-Gas service information


RegO L-545 LP-Gas Serviceman's Manual - cover page
Brand
REGO
Category
Other
Document type
Service Manual
Language
English
Pages
63
File format
PDF
File size
1.6 MB
Published
16 October, 2023
Updated
16 October, 2023
MD5 checksum
E37C75CE27217FD97472C437F5D91CFD

About this manual

This manual, published by RegO, serves as a handy reference for installation servicemen and others requiring information for field service work. It covers essential topics such as vapor pressures, installation planning, propane storage vessels, and proper purging of containers, ensuring safer and more efficient installations in accordance with NFPA 58 2020.

What's inside

  • Information About LP-Gas
  • Vapor Pressures of LP-Gases
  • Installation Planning
  • Propane Storage Vessels
  • Determining Total Load
  • Propane Vaporization Capacity Guide
  • Proper Purging of LP-Gas Containers
  • LP-Gas Regulators
  • Leak Testing the Installation
  • Pressure Relief Valves

Specifications

Chemical Formula (Propane)C3H8
Boiling Point (Propane)-44 ºF
Specific Gravity of Gas (Propane)1.50
Specific Gravity of Liquid (Propane)0.504
Lbs. per Gallon of Liquid (Propane)4.20
BTU per Gallon of Liquid (Propane)91502
BTU per Lb. of Gas or Liquid (Propane)21548
BTU per Cu. Ft. of Gas (Propane)2488
Cu. Ft. Vapor per Gal. Liq (Propane)36.38
Ignition Temperature in Air (Propane)920-1120 ºF
Maximum Flame Temperature in Air (Propane)3595 ºF
Lower Limit of Flammability (Propane)2.15 %
Upper Limit of Flammability (Propane)9.6 %
Octane Number (Propane)Over 100

Frequently asked questions

What is the approximate vaporization rate of a 100 lb. cylinder at 0ºF?

The approximate vaporization rate is 50,000 BTU per hour.

How is the total load determined for sizing storage containers?

The total load is the sum of all gas usage in the installation, arrived at by adding up the BTU input of all appliances.

How do you convert total BTU load to CFH for propane?

Divide the total BTU load by 2488 to get the CFH of propane.

What is the formula for calculating the BTU/hr capacity of an ASME container at 0ºF?

Multiply the overall diameter (D) by the overall length (L) by the K factor (D X L X K).

Download PDF (1.6 MB)