provide relevant LP-Gas service information
This manual, published by RegO, serves as a handy reference for installation servicemen and others requiring information for field service work. It covers essential topics such as vapor pressures, installation planning, propane storage vessels, and proper purging of containers, ensuring safer and more efficient installations in accordance with NFPA 58 2020.
| Chemical Formula (Propane) | C3H8 |
|---|---|
| Boiling Point (Propane) | -44 ºF |
| Specific Gravity of Gas (Propane) | 1.50 |
| Specific Gravity of Liquid (Propane) | 0.504 |
| Lbs. per Gallon of Liquid (Propane) | 4.20 |
| BTU per Gallon of Liquid (Propane) | 91502 |
| BTU per Lb. of Gas or Liquid (Propane) | 21548 |
| BTU per Cu. Ft. of Gas (Propane) | 2488 |
| Cu. Ft. Vapor per Gal. Liq (Propane) | 36.38 |
| Ignition Temperature in Air (Propane) | 920-1120 ºF |
| Maximum Flame Temperature in Air (Propane) | 3595 ºF |
| Lower Limit of Flammability (Propane) | 2.15 % |
| Upper Limit of Flammability (Propane) | 9.6 % |
| Octane Number (Propane) | Over 100 |
The approximate vaporization rate is 50,000 BTU per hour.
The total load is the sum of all gas usage in the installation, arrived at by adding up the BTU input of all appliances.
Divide the total BTU load by 2488 to get the CFH of propane.
Multiply the overall diameter (D) by the overall length (L) by the K factor (D X L X K).