The document introduces the specifications and features of the 48NDVA light column alarm display. The product features 101 light column points, isolated analog output, analog output function, 4-digit display, and the ability to set 4 alarms. It is suitable for typical applications such as wide-angle equipment replacement, input for collective alarm devices, analog value alarm contacts for sequential control, and alarms when the machine malfunctions.
The M-System 48NDVA is a light column alarm display designed for wide-view applications and replacement of collection-type alarm devices. It features 101 LED points for clear visibility from a distance and supports multi-color display options (red, amber, green). The unit includes an isolated analog output and allows for the setting of four alarm points: upper-upper limit, upper limit, lower limit, and lower-upper limit. The front panel meets the IP65 standard for protection against dust and water. This manual is written in Japanese.
| Light Column Points | 101 |
|---|---|
| Front Panel Protection | IP65 |
| Alarm Points | 4 points |
| Input Current Range | 0 to 50mA DC |
| Input Voltage Range | -10 to +10V DC |
| Output Current Range | 0 to 20mA DC |
| Operating Temperature | -5 to +55C |
| Mechanical Life | 5,000,000 times |
The input resistance must be 1MΩ or higher.
Yes, the brightness can be adjusted in 7 steps.
The range is from -1999 to 9999.